Inverter error codes
Error code | Remedy |
Grid Lost Fault | Grid is interrupted
|
Grid Volt Fault | Grid voltage outside the normal range
|
Grid Freq Fault | Grid frequency outside the normal range
|
PLL_OverTime | Three-phase system accesses single-phase alternating current
|
10min Volt Fault | Mains voltage has been outside the normal range for the last 10 minutes
|
SW Inv Cur Fault | High output current detected by the software
|
DCI Fault | The DC-related input current is outside the limit value
|
HW Inv Cur Fault | High output current detected by the hardware.
|
SW Bus Vol Fault | Out of range bus voltage detected by the software.
|
Bat Volt Fault | battery voltage error.
|
SW Bat Cur Fault | high battery current detected by the software.
|
Iso Fault | the insulation is faulty.
|
Res Cur Fault | the fault current is high.
|
Pv Volt Fault | PV voltage outside the tolerance range.
|
SW Pv Cur Fault | the software has detected a high PV input current.
|
Temp Fault | the temperature of the inverter is high.
|
Ground fault | the earthing is faulty.
|
Over Load Fault | Overload in grid operation.
|
Eps Over Load | Overload in grid replacement mode.
|
Bat Power Low | The battery power is low.
|
HW Bus Vol Fault | Bus voltage detected by the hardware is outside the standard range.
|
HW Pv Cur Fault | high PV input current detected by the hardware.
|
HW Bat Cur Fault | high battery current detected by the hardware.
|
SCI Fault | Communication between master and manager has failed.
|
MDSP SPI Fault | Communication between master and slave has failed.
|
MDSP Smpl Fault | The master sample detection circuit is failed. - Disconnect PV, grid and battery, then reconnect |
Res Cur HW Fault | residual current detection has failed.
|
Inv EEPROM Fault | The inverter EEPROM memory is faulty.
|
PvCon Dir Fault | The PV connections are reversed.
|
Bat Relay Open | the battery relay is open.
|
Bat Relay Short Circuit | the battery relay is closed.
|
Bat Buck Fault | the battery buck circuit mosfet is fail.
|
Bat Boost Fault | The battery boost circuit mosfet is fail or The relay on the battery side of the inverter is not closed. To upgrade to the latest software, at least ensure that the master is upgraded to 1.69 or above.
|
Eps Relay Fault | The EPS relay has failed.
|
BatCon Dir Fault | The battery connections are reversed.
|
Grid Relay Fault | The grid relay is open or closed.
|
RDSP SPI Fault | Communication between master and slave has failed.
|
RDSP Smpl Fault | The slave sample detection circuit is failed.
|
ARM EEPROM Fault | The EEPROM of the manager is faulty.
|
Meter Lost Fault | Communication between meter and inverter is interrupted.
|
BMS Lost | Communication between BMS and inverter is interrupted.
|
Bms Ext Fault | Communication between BMS and inverter is interrupted.
|
Bms Int Fault | dIP switch in the wrong position Communication between the battery packs is interrupted.
|
other error messages | Contact Solarwatt. |